E-mail


3 PHASE POWER CLAMP ON METER (TRMS) WITH KWHR-Kusam Meco-KM 2709
View Full-Size Image


3 PHASE POWER CLAMP ON METER (TRMS) WITH KWHR-Kusam Meco-KM 2709
Price per Unit (piece): Call for Pricing

Ask a question about this product



Display
:
Voltage Function : 6000 counts LCD display,
Power, Ohm & Hz functions : 9999 counts LCD display.
ACA clamp-on function : 4000 counts LCD display.
Update Rate
:
Power function : 2 per second nominal
Voltage, ACA clamp-on & Ohm functions : 2 per second nominal Hz function : 1 per second nominal
Polarity
:
Automatic
Low Battery
:
Below approx 2.4V
Operating Temperature
:
0oC to 40oC
Relative Humidity
:
Maximum relative humidity 80% for temperature
upto 31oC decreasing linearly to 50% relative humidity at 40oC
Altitude
:
Operating below 2000m
Storage Temperature
:
-20°C to 60°C, < 80% R.H. (With battery removed)
Temperature Coefficient
:
nominal 0.15x (specified accuracy) /°C
@ (0°C -18°C or 28°C - 40°C), or otherwise specified
Sensing
:
True RMS sensing
Power supply
:
Standard 1.5V AAA Battery x 2.
Power Consumption
:
Voltage, ACA, Hz &
Power functions : 11mA typical
Ohm function : 5.5mA typical
APO Timing
:
Idle for 30 minutes
APO Consumption
:
4µA typical
Dimension
:
224(L) x 78(W) x 40(H) mm
Weight
:
approx. 224 gms
Jaw opening & Conductor diameter
:
45mm max
Special features
:
Backlight display, AutoVATM (Auto Selection on ACV, DCV or ACA functions); selectable Power parameters of KW, KVAR & KVA with Total Power Factor in dual-display; Total harmonic distortion THD%-F in dual-display; kWHr Recording; Display Hold; PEAK-rms HOLD; PC-Comm computer interface capabilities
Accessories
:
Test leads (pair), batteries installed, user’s manual & soft carrying case
Optional Accessories
:
PC interface kit
Meets IEC61010-2-032(2002), EN61010-2-032(2002), UL61010B-2-032(2003)
Measurement Category
:
CATIII 600Volts AC & DC
Transient Protection
:
6.5kV (1.2/50µs Surge)
Pollution degree
:
2
E. M. C.
:
Meets EN61326(1997, 1998/A1), EN61000-4-2 (1995,2000/A2), and EN61000-4-3(2002)
In an RF field of 3V/m
:
Total Accuracy = specified Accuracy + 50 digits
Performance above 3V/m is not specified
Overload Protections
:
ACA Clamp-on jaws : AC 1000A rms continuous
+ & COM terminals : 600VDC/VAC rms